ANWENDUNG
The H05RN-F cable is a low voltage rubber sheathed power cable for flexible trailing applications. It is manufactured in accordance with VDE 0282 Part 4.
The H05RN-F cable is commonly specified on portable handheld household equipment, workshop tools such as soldering irons, furniture, and in the construction industry predominantly in pre-fabricated building parts. It has an operating temperature range of -40oC to +60oC and with its Polychloroprene (PCP) outer sheath it is both ozone resistant, oil resistant and flame retardant.
For general use in domestic premises, kitchens, offices and industrial equipment where the cables are subjected to low mechanical stress. Suitable for dry, damp and wet installations, including temporary outdoor power. Supply of electricity and communications in buildings and other civil engineering works with the objective of limiting the generation and spread of fire.
Technical Data
Voltage Rating U/Uo
300/500V
Operating
-40°C to +60°C
Permissible operating temperature of the conductor
+60°C
Minimum installation and use temperature
-25°C
Maximum temperature of short circuit
+200°C
Max. permissible operating voltage alternating current (WECHSELSTROM) conductor/earth
318 V
three-phase alternating current (WECHSELSTROM) conductor/conductor
550 V
direct current (GLEICHSTROM) conductor/earth
413 V
direct current (GLEICHSTROM) conductor/conductor
825 V
Test voltage core/core
2000 V
Minimaler Biegeradius
Fixed: 4 x Gesamtdurchmesser
Mobile: 6 x Gesamtdurchmesser
KONSTRUKTION
Dirigent
Klasse 5 flexibler Kupferleiter. acc. to DIN VDE 0295 Klasse 5 / IEC 60228 Klasse 5
Isolierung
EPD (Ethylen-Propylen-Kautschuk) EI4. acc. to DIN VDE 0207-363-1 / DIN EN 50363-1 (compound type EI4)
Scheide
PCP (Polychloroprene) EM2. acc. to DIN VDE 0207-363-2-1 / DIN EN 50363-2-1 (compound type EM2)
Core Identification acc. to DIN VDE 0293-308, colour coded
2 Kern: Blue Brown
3 Kern: Green/Yellow Blue Brown
4 Kern: Green/Yellow Brown Black Grey
Farbe der Scheide
Schwarz
NORMEN
IEC/DE 50525-2-21, CEI 20-107/2-21, CEI 20-19/4 (CENELEC HD 22.4 S4), BS 6500:2000, NF C 32-102-4, VDE 0282-4, DE 50575:2014 + EN 50575/A1:2016
Product features
Flame-retardant according
DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
Oil-resistant according
DE 60811-404
Notes
Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.
Here, the Class 5 flexible copper conductors are provided in 0.75mm2 and 1mm2 only. It is available in 2 Kern, 3 core and 4 core variants as standard. the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm2 |
MAXIMUM CONDUCTOR DURCHMESSER Mm |
NOMINAL THICKNESS OF INSULATION Mm |
NOMINAL OVERALL DIAMETER Mm |
NOMINAL WEIGHT kg/km |
|
Minimum | Maximum | |||||
2 | 0.75 | 0.95 | 0.6 | 5.7 | 7.4 | 44 |
2 | 1 | 1.3 | 0.6 | 6.1 | 8 | 55 |
3 | 0.75 | 0.95 | 0.6 | 6.2 | 8.1 | 60 |
3 | 1 | 1.3 | 0.6 | 6.5 | 8.5 | 72 |
4 | 0.75 | 0.95 | 0.6 | 6.8 | 8.8 | 82 |
4 | 1 | 1.3 | 0.6 | 7.1 | 9.3 | 87 |