ANWENDUNG
PVC panel wiring for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
CHARAKTEREIGENSCHAFTEN
Voltage Rating Uo/U
H05V-K: 300/500V
H07V-K: 450/750V
Temperatur-Einstufung
Fixed: -30°C to +70°C
Gebeugt: -5°C to +70°C
Minimaler Biegeradius
Fixed: 6 x Gesamtdurchmesser
NORMEN
DE 50525-2-31, DE 60228
Flame Retardant according to IEC/EN 60332-1-2
KONSTRUKTION
Dirigent
Klasse 5 flexibler Kupferleiter
Isolierung
PVC (Polyvinylchlorid)
Farbe der Isolierung
Rot, Schwarz, Blau, Orange, Gelb, Weiß, Grün/Gelb, Grau, Braun, Violett, Rosa.
H05V-K | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL OVERALL DIAMETER Mm |
NOMINAL WEIGHT kg/km |
0.5 | 2.2 | 9.1 | |
0.75 | 2.4 | 11.7 | |
1 | 2.55 | 14.4 |
H07V-K | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL OVERALL DIAMETER Mm |
NOMINAL WEIGHT kg/km |
1.5 | 3.00 | 20.1 | |
2.5 | 3.65 | 31.5 | |
4 | 4.2 | 46.2 | |
6 | 4.8 | 65.1 | |
10 | 6.25 | 109.4 | |
16 | 7.4 | 165.2 | |
25 | 9.4 | 253.4 | |
35 | 10.4 | 345.5 | |
50 | 12.55 | 492.4 | |
70 | 14.10 | 669.3 | |
95 | 17.20 | 910.4 | |
120 | 17.70 | 1129.4 | |
150 | 19.60 | 1401.0 | |
185 | 23.00 | 1741.0 | |
240 | 26.40 | 2267.5 |
WeChat
Scannen Sie den QR-Code mit wechat