Tel: +86-13167190983    E-mail: michael@shanghaiyunigroup.com

About   Contact    |   

8.7/15(17.5)KV XLPE INSULATION ARMORED POWER CABLE -

Medium Voltage Power Cable/Power Cable/

8.7/15(17.5)KV XLPE INSULATION ARMORED POWER CABLE

To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations, fixed installed in air, directly buried in the ground or in ducts, where require higher mechanical protection.

  • Product Details

Product Structure
1.Conductor- Plain class 2 compacted copper or Aluminum
2.Conductor Screen– Semi-conductive compound
3.Insulation- Cross linked polyethylene (XLPE)
4.Insulation Screen- Semi-conductive compound
5.Metallic Screen- Plain annealed copper tape
6.Filler- Non-hygroscopic material(For Three core)
7.Binder Tape- Non-hygroscopic material tape
8.Separation Layer- Polyvinyl chloride compound (PVC)
9.Armor- Galvanized steel wire for three core, aluminum wire for single core
10.Binder Tape- Non-hygroscopic material tape
11.Outer Sheath- Polyvinyl chloride compound (PVC)

Table1 Single core CU(AL)/XLPE/CTS/PVC/AWA/PVC

 

No.
& CSA
Conductor XLPE insulation Copper tape screen Aluminum wire armor Outer sheath Weight kg/km
Approx. diameter mm Nominal thickness mm Nominal thickness mm Nominal diameter of Aluminum wire mm Nominal thickness mm Diameter mm YJV72(CU) YJLV72(AL)
1*25 6.0 4.5 0.12 1.6 1.9 28.6 1109 957
1*35 7.0 4.5 0.12 1.6 1.9 29.6 1245 1032
1*50 8.2 4.5 0.12 1.6 1.9 30.8 1415 1128
1*70 10.0 4.5 0.12 2.0 2.0 33.6 1793 1371
1*95 11.6 4.5 0.12 2.0 2.1 35.4 2116 1536
1*120 13.0 4.5 0.12 2.0 2.1 36.8 2405 1674
1*150 14.6 4.5 0.12 2.0 2.2 38.6 2772 1860
1*185 16.2 4.5 0.12 2.0 2.2 40.2 3176 2038
1*240 18.4 4.5 0.12 2.0 2.3 42.6 3793 2318
1*300 20.6 4.5 0.12 2.5 2.4 46.2 4624 2780
1*400 23.8 4.5 0.12 2.5 2.5 49.6 5649 3237
1*500 26.6 4.5 0.12 2.5 2.6 53.1 6820 3758
1*630 30.0 4.5 0.12 2.5 2.7 56.7 8276 4358
1*800 34.0 4.5 0.12 2.5 2.9 61.3 10133 5146

 

Table2 Three core CU(AL)/XLPE/CTS/PVC/SWA/PVC

 

No.
& CSA
Conductor XLPE insulation Copper tape screen Steel wire armor Outer sheath Weight kg/km
Approx. diameter mm Nominal thickness mm Nominal thickness mm Nominal diameter of steel wire mm Nominal thickness mm Diameter mm YJV32(CU) YJLV32(AL)
3*25 6.0 4.5 0.1 2.50 2.7 52.5 4847 4387
3*35 7.0 4.5 0.1 2.50 2.8 55.0 5410 4769
3*50 8.2 4.5 0.1 2.50 2.9 57.8 6052 5185
3*70 10.0 4.5 0.1 2.50 3.0 62.1 7150 5879
3*95 11.6 4.5 0.1 2.50 3.1 65.8 8268 6519
3*120 13.0 4.5 0.1 2.50 3.2 69.2 9356 7151
3*150 14.6 4.5 0.1 3.15 3.4 74.6 11513 8762
3*185 16.2 4.5 0.1 3.15 3.5 78.2 12969 9540
3*240 18.4 4.5 0.1 3.15 3.7 83.6 15228 10782
3*300 20.6 4.5 0.1 3.15 3.8 88.7 17596 12038
3*400 23.8 4.5 0.1 3.15 4.1 96.4 21181 13908
3*500 26.6 4.5 0.1 3.15 4.3 103.8 25227 15995
3*630 30.0 4.5 0.1 3.15 4.5 111.7 30192 18379
3*800 34.0 4.5 0.1 3.15 4.8 121.2 36371 21337

 

 