Tel: +86-13167190983 E-mail: michael@shanghaiyunigroup.com

Despre Contact |

H05RN-F Cable - Shanghai Yuni Group

Fir electric/

H05RN-F Cable

H05RN-F Cable
Voltage: 300/500V
Structure: Dirijor Class 5 flexible copper conductor.
Insulation EPR (Ethylene Propylene Rubber) EI4
Jacket PCP (Polychloroprene) EM2
Feature Flexible cable

  • Detalii produs

APPLICATION

The H05RN-F cable is a low voltage rubber sheathed power cable for flexible trailing applications. It is manufactured in accordance with VDE 0282 Part 4.

The H05RN-F cable is commonly specified on portable handheld household equipment, workshop tools such as soldering irons, furniture, and in the construction industry predominantly in pre-fabricated building parts. It has an operating temperature range of -40oC to +60oC and with its Polychloroprene (PCP) outer sheath it is both ozone resistant, oil resistant and flame retardant.

For general use in domestic premises, kitchens, offices and industrial equipment where the cables are subjected to low mechanical stress. Suitable for dry, damp and wet installations, including temporary outdoor power. Supply of electricity and communications in buildings and other civil engineering works with the objective of limiting the generation and spread of fire.

Technical Data

Voltage Rating U/Uo

300/500V

Operating

-40°C to +60°C

Permissible operating temperature of the conductor

+60°C

Minimum installation and use temperature

-25°C

Maximum temperature of short circuit

+200°C

Max. permissible operating voltage alternating current (AC) conductor/earth

318 V

three-phase alternating current (AC) conductor/conductor

550 V

direct current (DC) conductor/earth

413 V

direct current (DC) conductor/conductor

825 V

Test voltage core/core

2000 V

Minimum Bending Radius

Fixed: 4 x overall diameter

Mobile: 6 x overall diameter

CONSTRUCTION

Dirijor

Class 5 flexible copper conductor. acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5

Insulation

EPR (Ethylene Propylene Rubber) EI4. acc. to DIN VDE 0207-363-1 / DIN EN 50363-1 (compound type EI4)

Teacă

PCP (Polychloroprene) EM2. acc. to DIN VDE 0207-363-2-1 / DIN EN 50363-2-1 (compound type EM2)

Core Identification acc. to DIN VDE 0293-308, colour coded

2 core: Blue Brown

3 core: Green/Yellow Blue Brown

4 core: Green/Yellow Brown Black Grey

Sheath Colour

Black

STANDARDS

IEC/EN 50525-2-21, CEI 20-107/2-21, CEI 20-19/4 (CENELEC HD 22.4 S4), BS 6500:2000, NF C 32-102-4, VDE 0282-4, EN 50575:2014 + EN 50575/A1:2016

Product features

Flame-retardant according

DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2

Oil-resistant according

EN 60811-404

Notes

Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.

Here, the Class 5 flexible copper conductors are provided in 0.75mm2 and 1mm2 only. It is available in 2 core, 3 core and 4 core variants as standard. the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

 

NO. OF
CORES
NOMINAL CROSS
SECTIONAL AREA
mm2
MAXIMUM CONDUCTOR
DIAMETER
milimetru
NOMINAL THICKNESS
OF INSULATION
milimetru
NOMINAL
OVERALL DIAMETER
milimetru
NOMINAL WEIGHT
kg/km
Minimum Maximum
2 0.75 0.95 0.6 5.7 7.4 44
2 1 1.3 0.6 6.1 8 55
3 0.75 0.95 0.6 6.2 8.1 60
3 1 1.3 0.6 6.5 8.5 72
4 0.75 0.95 0.6 6.8 8.8 82
4 1 1.3 0.6 7.1 9.3 87

 

 